Wire voltage drop calculator

Enter the wire size, one-way length, current and supply voltage to find how many volts the cable loses, what share of the supply that is, the voltage left at the load and the heat lost in the wire. Works for DC, single-phase and three-phase circuits, copper and aluminium.

Circuit
Conductor
Units
ft
A
V
Voltage drop1.588 V
Voltage drop in percent1.32 %
Voltage at the load
118.41 V
Resistance of one conductor
0.0794 Ω
Power lost in the cable
15.88 W
Cross-section of this gauge
3.309 mm²

Runs in your browser: nothing you enter is sent anywhere.

How to use

  1. Choose DC, single-phase or three-phase and the conductor material.
  2. Choose the units and enter the cross-section in mm² or pick the AWG gauge.
  3. Enter the one-way length of the cable — from the supply to the load, not the length of both wires.
  4. Enter the load current and the supply voltage (line-to-line for three-phase, for example 400 V).

Formulas

  • resistance of one conductor: R = ρ × L / A
  • DC and single-phase: drop = 2 × I × R, loss = I² × 2R
  • three-phase: drop = √3 × I × R, loss = 3 × I² × R
  • percent = drop / supply voltage × 100; voltage at the load = supply − drop

ρ = 0.017241 Ω·mm²/m for copper and 0.028264 Ω·mm²/m for aluminium at 20 °C. AWG sizes are turned into mm² with the AWG definition (12 AWG = 3.309 mm²).

Worked examples

Single-phase, 12 AWG copper, 50 ft one way, 10 A at 120 V: 50 ft = 15.24 m, R = 0.017241 × 15.24 / 3.309 = 0.0794 Ω. Drop = 2 × 10 × 0.0794 = 1.588 V, which is 1.32 %; the load gets 118.41 V and the cable turns 15.88 W into heat.

Single-phase, 2.5 mm² copper, 20 m, 10 A at 230 V: R = 0.1379 Ω, drop 2.759 V, or 1.2 %.

Three-phase, 16 mm² aluminium, 50 m, 32 A at 400 V: R = 0.028264 × 50 / 16 = 0.088325 Ω, drop = √3 × 32 × 0.088325 = 4.895 V, or 1.22 %.

Tips

  • Doubling the length doubles the drop; doubling the cross-section halves it.
  • Low-voltage circuits suffer most: the same 2 V that is under 1 % at 230 V is about 17 % at 12 V. Size 12 V and 24 V wiring by voltage drop, not only by current.
  • Voltage drop is a separate check from current capacity: a wire can be thick enough not to overheat and still lose too many volts over a long run.

Frequently asked questions

How is the voltage drop calculated?

The resistance of one conductor is R = ρ × L / A, with the one-way length L in metres and the cross-section A in mm². In DC and single-phase circuits the current flows out and back, so the drop is 2 × I × R. In a balanced three-phase circuit the line-to-line drop is √3 × I × R.

Which resistivity values are used?

Annealed copper 0.017241 Ω·mm²/m and aluminium 0.028264 Ω·mm²/m, both at 20 °C. A wire running hot has more resistance (copper about 0.4 % more per °C), so the real drop under full load is somewhat larger.

What voltage drop is acceptable?

Wiring rules set the limits and they differ by country and by type of circuit. Figures of 3 % for a final circuit and 5 % from the supply to the furthest load are common recommendations; check the rules that apply to your installation.

Does the calculator include reactance and power factor?

No. It counts only the resistance of the conductors. For the cable sizes and lengths of ordinary buildings that is the main part; for large cables, long runs or motors with a low power factor the reactive part adds to the drop.