UPS runtime calculator

Enter the voltage and amp-hour rating of the UPS batteries, how many there are, and the load in watts (or VA with a power factor). Adjust the inverter efficiency and how deep you allow the batteries to discharge. The calculator estimates the runtime and the stored and usable energy.

V
Ah
Load given in
%
%
Estimated runtime46.7 min
Estimated runtime in hours
0.78 h
Stored energy
216 Wh
Energy delivered to the load
155.5 Wh
Battery current
9.26 A

Runs in your browser: nothing you enter is sent anywhere.

How to use it

  1. Enter the voltage and Ah of one battery and the number of batteries (UPS packs are wired in series: two 12 V batteries make 24 V).
  2. Enter the load in watts, or choose VA and give the power factor.
  3. Keep or change the inverter efficiency (90 % is a typical starting value) and the usable depth of discharge.
  4. Read the runtime in minutes and hours, the stored and usable energy and the current the batteries supply.

Formula

  • Stored energy E = V × Ah × n (Wh)
  • Usable energy = E × DoD × η
  • Runtime t = usable energy / P (hours), × 60 for minutes
  • Load in watts P = VA × PF when given in VA
  • Battery current I = P / (η × V × n)

Worked example

A small UPS has two 12 V 9 Ah batteries and powers a 200 W load. The stored energy is 12 × 9 × 2 = 216 Wh. Using 80 % of it with a 90 % efficient inverter leaves 216 × 0.8 × 0.9 = 155.52 Wh for the load, so the runtime is 155.52 / 200 = 0.78 h ≈ 46.7 minutes. The batteries supply 200 / (0.9 × 24) = 9.26 A.

A 500 VA load at power factor 0.6 is 300 W; on four 12 V 7 Ah batteries (336 Wh, 85 % efficiency, 80 % DoD) it runs about 45.7 minutes.

Tips

  • Halving the load more than doubles the runtime in practice, because batteries deliver more of their capacity at lower current.
  • Shut down gracefully. Plan the runtime you need to save work and power off, plus a margin, not the theoretical maximum.
  • Replace old batteries. Sealed lead-acid UPS batteries lose capacity over a few years; a runtime test tells you when.

Frequently asked questions

How do I calculate UPS runtime?

Runtime (h) = battery V × Ah × number of batteries × depth of discharge × inverter efficiency ÷ load in W. Two 12 V 9 Ah batteries, 80 % usable, 90 % efficiency and a 200 W load: 216 × 0.8 × 0.9 / 200 = 0.78 h, about 47 minutes.

How do I convert VA to watts?

Multiply by the power factor: W = VA × PF; a device label or a plug-in power meter gives the real watts directly. If the UPS label shows both VA and W, size against the W figure.

Why is the real runtime shorter than calculated?

Lead-acid batteries deliver less than their nameplate Ah at high current (the rating is usually for a 20-hour discharge), and capacity falls with age and cold. At loads near the UPS limit expect noticeably less than this simple energy estimate.

What depth of discharge should I use?

For a UPS that runs the battery flat in an outage, 80 to 100 % gives the immediate runtime. If you want the batteries to last many cycles, plan on using less; lithium batteries tolerate deeper discharge than lead-acid.

More in Unit converters

All tools in this category: Unit converters ·Updated November 7, 2026