Power factor correction calculator

Enter the real power of the load in kW, its present power factor and the power factor you want to reach, then the supply voltage and frequency. The calculator gives the reactive power the capacitors must supply, their capacitance, and how much the apparent power and current drop.

kW
Supply
V
Frequency
Capacitor reactive power Qc55.32 kvar
Capacitance per phase, delta bank
366.9 µF
Capacitance per phase, star bank
1,100.6 µF
Apparent power before
133.33 kVA
Apparent power after
105.26 kVA
Reactive power before
88.19 kvar
Line current before
192.45 A
Line current after
151.93 A
Current reduction
21.05 %

Runs in your browser: nothing you enter is sent anywhere.

How to use it

  1. Enter the real power of the load in kW (from a meter or the nameplate).
  2. Enter the present power factor and the target, for example 0.75 and 0.95.
  3. Choose three phase or single phase, the voltage (line-to-line for three phase) and the frequency.
  4. Read the capacitor kvar, the capacitance per phase for a delta or star bank (or the single capacitor), and the current before and after.

Formulas

  • φ = arccos(PF); Qc = P × (tan φ₁ − tan φ₂) kvar
  • Apparent power S = P / PF kVA
  • Current: I = S / V single phase, I = S / (√3 × V) three phase
  • Capacitance (ω = 2πf): single phase C = Qc / (ωV²); three phase delta C = Qc / (3ωV²) per phase; star C = Qc / (ωV²) per phase

Worked example

A 100 kW load at 0.75 power factor on 400 V, 50 Hz three phase, corrected to 0.95. tan φ₁ = √(1 − 0.75²) / 0.75 = 0.8819 and tan φ₂ = 0.3287, so the bank must supply 100 × (0.8819 − 0.3287) = 55.32 kvar. With ω = 314.16, a delta bank needs 55,323 / (3 × 314.16 × 400²) = 366.9 µF per phase (a star bank 1,100.6 µF).

The apparent power falls from 133.33 to 105.26 kVA and the line current from 192.45 A to 151.93 A, 21.05 % less.

Tips

  • Capacitors are sold in kvar at a rated voltage; choose a rating at or above your supply voltage and the nearest step at or below the calculated kvar.
  • Correct at the motor or centrally. Individual correction cuts current all the way back to the board; a central automatic bank follows a changing load.
  • Harmonics change the picture. With variable-speed drives or other non-linear loads, capacitors can resonate with the supply; such cases need detuned banks and a harmonic study.

Frequently asked questions

How do I calculate the kvar for power factor correction?

Qc = P × (tan φ₁ − tan φ₂), where φ = arccos(PF). For 100 kW from 0.75 to 0.95: tan φ₁ = 0.8819, tan φ₂ = 0.3287, so Qc = 100 × 0.5532 = 55.32 kvar.

How do I convert kvar to microfarads?

From Q = 2πf·C·V²: C = Q / (2πf·V²). In three phase with V the line voltage, a delta-connected bank needs Q / (3 × 2πf × V²) per capacitor; a star bank needs three times that capacitance, because each capacitor sees only V/√3.

What power factor should I aim for?

A common target is 0.95: it already cuts the current noticeably. Going to 1.0 costs more capacitance for little gain and risks over-correction when the load drops.

Why does the current fall after correction?

The real power stays the same, but the apparent power S = P / PF falls, and the current is proportional to S. From 0.75 to 0.95 the current drops by 1 − 0.75/0.95 = 21 %, which cuts cable losses and frees transformer capacity.