Transformer short circuit current calculator

Enter the transformer rating in kVA, the secondary voltage and the impedance from the nameplate in percent. Leave the supply fault level at 0 for an infinite source, or enter it in MVA for a less conservative figure. The result is the maximum current a bolted fault at the terminals would draw.

kVA
V
%
Transformer
MVA
Short circuit current28.87 kA
Short circuit current in amperes
28,868 A
Full-load current
1,443.4 A
Fault level at the terminals
20 MVA
Fault current ÷ full-load current
20

Runs in your browser: nothing you enter is sent anywhere.

How to use it

  1. Enter the transformer rating in kVA and its secondary voltage (line-to-line for three phase).
  2. Enter the impedance Z% from the nameplate, often around 4 to 6 % for distribution transformers.
  3. Choose three phase or single phase.
  4. Leave the supply fault level at 0 for a worst-case infinite source, or enter it in MVA if the utility has given it.

Formula

  • Full-load current: I_FL = S / (√3 × V) three phase, S / V single phase
  • Transformer impedance in per unit: z = Z% / 100
  • Supply impedance on the transformer base: z_s = S_T / S_sc (0 for an infinite source)
  • Short circuit current: I_sc = I_FL / (z + z_s)
  • Fault level: S_T / (z + z_s)

Cable impedance and motor contribution are not included.

Worked example

A 1000 kVA, 400 V, 5 % transformer on an infinite source: I_FL = 1,000,000 / (1.7321 × 400) = 1443.4 A. The short circuit current is 1443.4 / 0.05 = 28,868 A = 28.87 kA, 20 times full-load current, a fault level of 20 MVA.

With a 500 MVA supply, z_s = 1/500 = 0.002 and the total is 0.052: I_sc = 1443.4 / 0.052 = 27.76 kA (19.23 MVA).

Tips

  • Breaking capacity: the breakers and fuses on the secondary side must have a rated breaking capacity above the prospective fault current at their location.
  • Lower Z%, higher fault current. A low-impedance transformer regulates voltage better but raises the fault level.
  • Check the voltage you enter. Line-to-neutral instead of line-to-line voltage in the three-phase formula overstates the current by √3.

Frequently asked questions

How do I calculate transformer short circuit current?

First the full-load current: I_FL = kVA × 1000 / (√3 × V) for three phase. Then I_sc = I_FL × 100 / Z%. A 1000 kVA, 400 V, 5 % transformer: I_FL = 1443.4 A, I_sc = 1443.4 / 0.05 = 28,868 A, about 28.9 kA.

What does the impedance percentage mean?

Z% is the voltage, as a percentage of rated voltage, that drives full-load current through the shorted secondary. At 5 %, full voltage drives 100/5 = 20 times full-load current.

Why include the supply fault level?

The infinite-source assumption ignores the impedance of the network upstream, so it slightly overstates the fault current. Adding the utility's fault level in MVA adds its impedance in series: 500 MVA ahead of a 1000 kVA, 5 % transformer lowers the fault from 28.87 to 27.76 kA.

Is this the value to choose breakers by?

It is the maximum at the transformer terminals and a starting point. Cable impedance lowers the current further along, and running motors can add to it during the first cycles; a full study per your local standard (for example IEC 60909) accounts for those.